Final | 12/7/2005 | 12/8/2005 | 12/8/2005 | A | PASS |
Pat Lass
|
|
|
Final inspection Nick Avery ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson
|
Electrical Rough-In | 11/23/2005 | 11/23/2005 | 11/23/2005 | P | PASS |
Bob Reichert
|
|
|
Ceiling inspection; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson corrections made, clg cover ok
|
Electrical Rough-In | 11/22/2005 | 11/22/2005 | 11/22/2005 | P | FAIL |
Bob Reichert
|
|
|
Ceiling inspection Pink Salon 6914 W. State; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, left corr notice, told ok to cover part of clg since he would call for am inspection, 330.30(B) mc cable shall be secured within 12" of box, 358.30(A) emt shall be secured within 3' of box, 210.62 show window recpt shall be added to east of door,725.3(B) abandoned lv cable shall be removed
|
Electrical Rough-In | 10/10/2005 | 10/11/2005 | 10/11/2005 | A | PASS |
Mike Kinnear
|
|
|
walls; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson ok cover walls only
|
Electrical Rough-In | 9/28/2005 | 9/28/2005 | 9/28/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson bath only ok to cover
|