Final | 9/6/2007 | 9/7/2007 | 9/7/2007 | A | FAIL |
Jack Frank
|
|
|
Please call Jim 30 min. prior@###-####. Phone #: ###-#### Internet Inspection Request from: Heather Packer corr fee due met contr. 210.52(C)(1)&(5) except shall install outlets for countertops and peninsular as codes noted states kit layout was changed after r/i inspection250.32 (B)(1) shall install phases,neut.,m and equip grd from service on fence to house, 250.52(A)(1) grd u/g water at house within 5ft, install 2 grd rods, 225.31,32,36 install service disconnect at either inside or outside upon entry , BCC&110.3(B) secure p/s at fence, and use only 2 pole breakers at milbank COW
|
Permanent Service | 9/7/2007 | 9/7/2007 | 9/7/2007 | A | FAIL |
Jack Frank
|
|
|
Please call Jim 30 min. prior@###-####. Phone #: ###-#### Internet Inspection Request from: Heather Packer see note for final inspection
|
Electrical Rough-In | 9/29/2005 | 9/30/2005 | 9/30/2005 | A | PASS |
Bob Reichert
|
|
|
Please call Tim for access 1/2 hr. before @ ###-####. Questions please call Jim @ ###-####. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer ric ok kitchen and bath, will call for more later
|