Final | 3/24/2006 | 3/27/2006 | 3/27/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok no card
|
ELE-Aging Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 | | NR |
Jack Frank
|
|
|
checked no power to p/s cannot final
|
ELE-Aging Inspection | 12/7/2005 | 12/7/2005 | 12/7/2005 | | NR |
Jack Frank
|
|
|
no power yet cannot check for final
|
Permanent Service | 10/7/2005 | 10/7/2005 | 10/7/2005 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack p/s u/g n ok
|
Permanent Service | 10/6/2005 | 10/6/2005 | 10/6/2005 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack cor.posted called correction not made 250.64(C) 250.30 FPN,see250.104(D) fee due
|
Permanent Service | 10/4/2005 | 10/4/2005 | 10/4/2005 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack cor. posted called,250.30(A)(7)&250.64(C) electrode from 120/240 panel shall be continuous, 250.56 test or 2 grd rods required, 250.29 needs bond bushung at 120/240 panel
|