Final | 5/15/2006 | 5/15/2006 | 5/15/2006 | P | PASS |
Bob Reichert
|
|
|
Kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
Rough-In Permanent Service | 11/14/2005 | 11/15/2005 | 11/15/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 11/10/2005 | 11/14/2005 | 11/14/2005 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called contr, left corr notice,334.30 nm cable shall be stapled wthin 12" of box,314.17(C) nm shall be stapled within 8" of box,300.4(A)&(D) bored holes and cable shall be 1 1/4" from edge of framing member,800.133(A) comm cable shall not be run with power wiring, 312.5 abrasion protection shall be provided for conductors entering enclosures.
|