Final | 1/25/2007 | 1/25/2007 | 1/25/2007 | P | PASS |
Bob Reichert
|
|
|
cody; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
Final | 1/24/2007 | 1/24/2007 | 1/24/2007 | P | FAIL |
Bob Reichert
|
|
|
cody or ###-#### call 1st for access code; Phone #: ###-#### Internet Inspection Request from: Victoria Beall please call Max Brown 1st so he can be there ###-#### met contr, left corr notice, NEC 410.8 fixture in closet shall be 12" from edge of shelf, 110.3(B) front recpt shall be installed per mfgr's instructions, BCC all equipment shall be mounted abd installed, wiring faults shall be repaired- entry ckt
|
Electrical Rough-In | 3/22/2006 | 3/23/2006 | 3/23/2006 | A | PASS |
Jack Frank
|
|
|
Re-inspection; Phone #: ###-#### Internet Inspection Request from: TJ Sturges r/i ok corr. made
|
Rough-In Permanent Service | 1/11/2006 | 1/12/2006 | 1/12/2006 | A | FAIL |
Jack Frank
|
|
|
nicole or steve ###-####; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor not made nail plates, and 11/4", 410.8 clearence rm over garage closet light, 110.3 replace service wires that are damaged by ringing the wire, boxes east kit wall set back 4" called
|
Electrical Rough-In | 10/19/2005 | 10/20/2005 | 10/20/2005 | A | FAIL |
Jack Frank
|
|
|
###-#### - nichole cor. called left message 314.16 box fill 300.4 nail pltes and 11/4", 410.8 clearence closet light upstairs bed rm over garage, 250.148 splice all equip grds 12 1nd 14 together
|