Final | 11/30/2005 | 11/30/2005 | 11/30/2005 | P | PASS |
Bob Reichert
|
|
|
chris --call 1st before insp for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left survey,352.30(A) rnc shall be strapped within 3' of panel, 440.22(C) a/c brkr shall be max 25A, ok to final
|
Electrical Rough-In | 10/25/2005 | 10/25/2005 | 10/25/2005 | P | PASS |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, ric ok, p/s u/g n ok
|
Electrical Rough-In | 10/24/2005 | 10/24/2005 | 10/24/2005 | P | FAIL |
Bob Reichert
|
|
|
###-#### - chris called contr, left corr notice, 210.52(A)(2) recpts shall be installed by door and under counter, 312.5 gec shall have abrasion protection, 334.80 shall derate conductors if over 2 in hole to be caulked over panel,BCC all make-up shall be done
|