Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE05-03867
StatusFinaled
Name C H ELECTRIC
Site Address 2811 N JEREMY AVE
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/30/200511/30/200511/30/2005PPASS
DetailsBob Reichert
chris --call 1st before insp for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left survey,352.30(A) rnc shall be strapped within 3' of panel, 440.22(C) a/c brkr shall be max 25A, ok to final
Electrical Rough-In10/25/200510/25/200510/25/2005PPASS
DetailsBob Reichert
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, ric ok, p/s u/g n ok
Electrical Rough-In10/24/200510/24/200510/24/2005PFAIL
DetailsBob Reichert
###-#### - chris called contr, left corr notice, 210.52(A)(2) recpts shall be installed by door and under counter, 312.5 gec shall have abrasion protection, 334.80 shall derate conductors if over 2 in hole to be caulked over panel,BCC all make-up shall be done