Final | 12/21/2005 | 12/22/2005 | 12/22/2005 | P | PASS |
Pat Lass
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no card
|
Final | 12/20/2005 | 12/21/2005 | 12/21/2005 | P | FAIL |
Pat Lass
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles GFCI protect receps to the right of the kitchen sink and within 6 ft. of wetbar sink. install recep within 12 in. of counter top on island counter. bathroom recep circuit shall not have lights on it.
|
Electrical Rough-In | 11/7/2005 | 11/8/2005 | 11/8/2005 | A | PASS |
Pat Lass
|
|
|
jeff Note: cover; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Permanent Service | 11/8/2005 | 11/8/2005 | 11/8/2005 | P | PASS |
Pat Lass
|
|
|
jeff Note: cover; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles P/S O/H R Ok
|
Electrical Rough-In | 11/4/2005 | 11/7/2005 | 11/7/2005 | A | FAIL |
Pat Lass
|
|
|
cover inspection//jeff; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa kitchen recep on dishwasher dieposal circuit. parallel protection of romex several locations. LB to sub panel undersized add receps. on 2 walls
|