Permit Information
Permit NumberELE05-03916
StatusFinaled
Name UNITED ELECTRIC CONTRACTING
Site Address 8800 W EMERALD ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: NEW X-FORMER AND DISC FOR NEW CT SCANNER
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/27/20067/28/20067/28/2006APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL corr made, ok to final
Final7/27/20067/27/20067/27/2006PCANC
DetailsJim Schmer
FINAL RE-INSPECTION FOR CT SCANNER; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL Inspection cancelled from web by: JENNY EMEL
ELE-Aging Inspection7/13/20067/13/20067/14/2006 DONE
DetailsBob Reichert
under design review from mfgr
ELE-Aging Inspection5/11/20065/11/20065/11/2006 DONE
DetailsBob Reichert
met elect, he will get with owner and only allow 2 weeks to fix correction notice or lock out power
Electrical Rough-In3/9/20063/10/20063/10/2006PCANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL wrong number, see ele06-00179
Conference1/12/20061/12/20061/12/2006PDONE
DetailsBob Reichert
MEET ELECTRICIAN TO DISCUSS ALTERNATE FOR CORD ON CT SCAN; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL talked about corr notice and need to get field evaluation for x-ray machine. Also installation to be per mfgrs instructions.
Final1/11/20061/11/20061/11/2006PFAIL
DetailsBob Reichert
called contr, left corr notice, contr had us look at data for cable, but the ampacity did not agree with NEC. Also data appeared to be generic for several types x-ray machines. Told contr he should disconnect power until evaluation was done. BCC 4-05-33(A) Equipment shall be listed as an assembly,450.13(B) transformer shall be readily accessible,400.5(A) st cord ampacity shall be per disconnect,400.8(1) cord shall not be used for fixed wiring,517.78shall apply for grounding ,517.13 shall apply for redundant gndg,250.118 shall apply for equipment gndg,110.2 equipment shall be acceptable only if approved
Final11/29/200511/30/200511/30/2005ACANC
DetailsBob Reichert
ELECTRICIAN TO MEET BOB AT 7:00AM TO GAIN ACCESS TO AREA.; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL see conf.
Conference11/30/200511/30/200511/30/2005PDONE
DetailsBob Reichert
ELECTRICIAN TO MEET BOB AT 7:00AM TO GAIN ACCESS TO AREA.; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL met elect and talked about 450.13(B) 75 kva xfmr shall be readily accessible, not in ceiling, type st cord with #2 conductors shall not be used due to ampacity per 400.5(A). 400.8(1) shall not use cord as substitute for fixed wiring of structure.517.78 shall apply for grounding requirements. 517.13 shall apply to redundant grounding. 250.118 shall apply for equipment grounding. Listed equipment shall show requirements for ampacity due to discrepancy of transformer size, equipment load requirements and material supplied with equipment. Will cancel final inspection request until information is obtained.
Final11/29/200511/29/200511/29/2005PNH
DetailsMike Kinnear
FINAL NEEDED FOR POWER TO NEW CT SCANNER IN IMAGING DEPT. X-FORMER ABOVE CEILING, DISC ON WALL IN CONTROL ROOM.; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL no access butch to make an appointment with 370 to show the work that was done