Temporary Service | 11/23/2005 | 11/23/2005 | 11/23/2005 | P | PASS |
Bob Reichert
|
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, t/s o/h n ok
|
Temporary Service | 11/16/2005 | 11/16/2005 | 11/16/2005 | P | FAIL |
Bob Reichert
|
|
|
vivian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, 110.12(A), unused openings shall be closed, 408.4 shall provide circuit directory, 250.53(G) gnd rod shall be flush with ground, 110.12(C) there shall be no contamination of internal parts, shall supply gfci recpts
|