Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE05-04164
StatusFinaled
Name ASAP ELECTRIC
Site Address 9801 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReview 
Description
11/16/2005 - wire in 6 new vaccuums & change service on pole from 100 amp to 200 amp - $4,000 per initial cert of value - cmc ///Final value is $3,500//2/1/06 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/4/20061/5/20061/5/2006APASS
DetailsBob Reichert
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
Final11/30/200511/30/200511/30/2005PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 11/30/2005 at 7:54:17 AM. Contact: ###-####. 312.5 abrasion protection shall be provided for conductors entering enclosure,250.53(B) gnd electrodes shall be min 6' apart, called contr, left corr notice
Electrical Rough-In11/18/200511/21/200511/21/2005APASS
DetailsPat Lass
Scheduled by a contractor via Hello! on 11/18/2005 at 1:16:06 PM. Contact: ###-####.
U/g Ok
Electrical Rough-In11/18/200511/18/200511/18/2005PFAIL
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 11/18/2005 at 8:49:58 AM. Contact: ###-####. nec 300.3 24inch under drive way