Temporary Service | 12/5/2005 | 12/5/2005 | 12/5/2005 | P | PASS |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, t/s u/g n ok
|
Temporary Service | 11/29/2005 | 11/30/2005 | 11/30/2005 | A | FAIL |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, corr not made,
|
Temporary Service | 11/23/2005 | 11/23/2005 | 11/23/2005 | P | FAIL |
Bob Reichert
|
|
|
###-####-chris called contr, left corr notice, 408.38 panel shall be dead front,312.5 conductors entering enclosure shall have abrasion protection,250.52(A)(5)(b) ground rod shall be 5/8" diameter, fee due
|