Final | 8/15/2006 | 8/16/2006 | 8/16/2006 | A | PASS |
Mike Kinnear
|
|
|
lamar west Internet Inspection Request from: Darla Downs ok final
|
Final | 8/15/2006 | 8/15/2006 | 8/15/2006 | P | NR |
Mike Kinnear
|
|
|
sharon; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley missing gfci in kitchen
|
Electrical Rough-In | 6/20/2006 | 6/21/2006 | 6/21/2006 | A | PASS |
Mike Kinnear
|
|
|
sharon ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok cover ri note need to add 3 rooms to permit owner to take care of it
|
Electrical Rough-In | 12/22/2005 | 12/23/2005 | 12/23/2005 | A | FAIL |
Jack Frank
|
|
|
lamar - no phone # Internet Inspection Request from: Letitia Mesa cor. met owner 210.12 afci for bed rms, 250.148 grd all metal boxes, 300.4 nail plates and 11/4",314.16 box fill, 300.14 6" free lenght, complete all makeup, 210.52(A) outlet spacing, 210.52(B&C) address wiring in kit. ,314.43 no screws or nails in plastic boxes,314.17 use approved connectors for romex, 240.24and BCC overcurrent devices higher than 6ft 7", update permit for work in 7rms not 2 rms, 10 days to correct violations , uncover all wiring covered before inspection, or power may be disconnected, if more violations created permit may be voided, and owner required to secure contractor staple romex within 8 or 12 inches of boxes, seal all unused KOs
|