Final | 12/13/2005 | 12/19/2005 | 12/19/2005 | A | PASS |
Bob Reichert
|
|
|
Good Morning Jack!!! We performed the grounding correction. Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell corr made, ok to final
|
Rough-In Permanent Service | 12/6/2005 | 12/7/2005 | 12/7/2005 | P | PART |
Jack Frank
|
|
|
We are upgrading the service to 200 amps on the exterior of the house and are replacing the indoor panel also. Idaho Power is killing the power in the AM so we can do this work and we will need you to inspect in the PM so they will re-energize. We will call you when we are done or you can call us when you have time to head that way. THANKS !!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cor. called 250.52,104(A)(1) grd or bond water system 250.66 shall be #4 copper p/s o/h rec. ok
|