Final | 11/22/2006 | 11/24/2006 | 11/24/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr made, ok to final
|
Final | 11/22/2006 | 11/22/2006 | 11/22/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot told elect, left corr notice, nec 110.26(A)(1) shall have 36" work depth in front of panels
|
ELE-Aging Inspection | 10/3/2006 | 10/3/2006 | 10/3/2006 | | PART |
Jack Frank
|
|
|
wsuc
|
Permanent Service | 4/7/2006 | 4/7/2006 | 4/7/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr. made p/s u/g new ok
|
Rough-In Permanent Service | 4/6/2006 | 4/6/2006 | 4/6/2006 | P | PART |
Jack Frank
|
|
|
barbara ###-####//final insp was supposed to be R/I ok only no p/s corr. 250.24(A)(1) shall terminate GEC at neutral bus not equip. grd. bus called
|
Final | 4/6/2006 | 4/6/2006 | 4/6/2006 | P | CANC |
Jack Frank
|
|
|
Thanks for you patience on this project. It's been a real trial for all of us.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
|
Rough-In Permanent Service | 4/5/2006 | 4/6/2006 | 4/6/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corrections not made still needs nail plates, and 250.24(A)(1) GEC shall terminate too neutral bus not equip grd bus called
|
Rough-In Permanent Service | 3/31/2006 | 3/31/2006 | 3/31/2006 | P | FAIL |
Jack Frank
|
|
|
Address will be painted on side this morning; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr. called 210.25 needs common area panel and branch circuits for stair lighting, 110.3(A&B) min. amps for electric heat 52 amp they only have 50, 300.4 nail plates and 11/4" everywhere, 334.30 cables stapled on egde, 220.84 calcs for p/s and feeders too apartments all electric also need plans at each building
|
Rough-In Permanent Service | 3/30/2006 | 3/31/2006 | 3/31/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called no address on building and the site is a mud and water hole
|
ELE-Aging Inspection | 3/14/2006 | 3/14/2006 | 3/14/2006 | | PART |
Jack Frank
|
|
|
called wsuc
|