Final | 4/6/2006 | 4/7/2006 | 4/7/2006 | A | PASS |
Bob Reichert
|
|
|
mikr; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles most corrections made, left survey 110.3(B) 15 x 20 access shall be provided for jetted tub access per mfgrs instructions
|
Final | 4/5/2006 | 4/6/2006 | 4/6/2006 | A | FAIL |
Jack Frank
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr. called 210.52(A&B) needs outlets in kit left of pantry door, and left of counter in nook by stair rails for wall space, 110.3(B) j tub manufactures requires 15"X20" access, 210.8 needs gfci outlet countertop butlers pantry, 250.104(A)(1) and 250.66 needs to bond copper water to p/s and bond hot and cold with #2 copper
|
Rough-In Permanent Service | 12/21/2005 | 12/22/2005 | 12/22/2005 | A | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 12/20/2005 | 12/20/2005 | 12/20/2005 | P | FAIL |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called, left message, left corr notice,334.80 over 2 nm cables in draft stopped hole shall be derated, 312.5 conductors entering enclosures shall be protected from abrasion, 300.4(A) & (D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 725.55 cl 2 & 3 cable shall not be run with class 1 conductors, 110.14 splices shall be properly installed and used (crimper), BCC job id sticker shall be posted, address shall be posted, approved set of plans shall be on job
|