Electrical Rough-In | 2/8/2006 | 2/9/2006 | 2/9/2006 | A | CANC |
Bob Reichert
|
|
|
underground inspection; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook met contr, wrong permit no.
|
DOC - Permit Finaled | | | 2/9/2006 | | DONE |
|
|
|
Insp was requested on the wrong permit ele05-04540 and should be finaled 2-9-06 eus
|
Temporary Service | 1/5/2006 | 1/6/2006 | 1/6/2006 | P | PASS |
Jack Frank
|
|
|
Insp was requested on the wrong permit ele05-04540 eus 2-9-06
|
Temporary Service | 12/20/2005 | 12/21/2005 | 12/21/2005 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, left corr notice, 250.66 gec shall be min #6, 590.6 recpt shall be gfci, 590.6(B)(1) 50a recpts shall be gfci, 406.8(B)(1),(2) recpts shall have in-use covers
|