Final | 6/5/2006 | 6/5/2006 | 6/5/2006 | P | PASS |
Bob Reichert
|
|
|
angie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
ELE-Aging Inspection | 5/25/2006 | 5/25/2006 | 5/26/2006 | | NR |
Bob Reichert
|
|
|
called,waiting for dishwasher, suc
|
ELE-Aging Inspection | 3/23/2006 | 3/23/2006 | 3/23/2006 | | DONE |
Bob Reichert
|
|
|
called contr to see if done, but suc
|
Electrical Rough-In | 1/5/2006 | 1/6/2006 | 1/6/2006 | A | PASS |
Bob Reichert
|
|
|
###-#### - seth corr made, ok to cover walls and clg
|
Electrical Rough-In | 1/3/2006 | 1/4/2006 | 1/4/2006 | A | FAIL |
Bob Reichert
|
|
|
ANGELA; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 300.4(D) mc cable shall be 1 1/4" from edge of framing member, 330.30(B) mc cable shall be secured within 12" of box, 314.4 metal box shall be grounded, 314.23 (B)(1) nails and screws used as fastening means shall be attached using brackets or within 1/4" of back or ends of enclosure,314.23(C) enclosure shall be rigidly secured
|