DOC - Permit Finaled | | | 4/14/2006 | | |
|
|
|
expire permit per Pat L., they only did service other company did building refer to Ele06-00919
|
Permanent Service | 1/30/2006 | 1/30/2006 | 1/30/2006 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 1/30/2006 at 7:14:02 AM. Contact: ###-####. P/S U/G N Ok
|
Permanent Service | 1/25/2006 | 1/26/2006 | 1/26/2006 | A | FAIL |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 1/25/2006 at 12:25:16 PM. Contact: ###-####. strap pvc. bond nipple between ct can and 600a panelboard. tap external for GEC also proper connectors either plastic Romex or listed for GEC. provide light and a way to use power.
|
Conference | 12/23/2005 | 12/27/2005 | 12/27/2005 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/23/2005 at 2:59:29 PM. called contractor not ready needs a plan first, of service layout
|