Final | 6/5/2006 | 6/6/2006 | 6/6/2006 | A | PASS |
William E Thomas
|
|
|
LARRY; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
|
Final | 6/2/2006 | 6/2/2006 | 6/2/2006 | P | FAIL |
Jack Frank
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not made called fee due
|
Final | 6/1/2006 | 6/1/2006 | 6/1/2006 | P | FAIL |
Jack Frank
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called 410.8 install closet fixture , provide required clearence,314.16 box fill end of pen. counter, 406.4(A B D) all areas, 408.4 panel schedule shall note location and specific purpose of circuits, does catv cabinet in attic access in closet require power? if so wire it
|
Rough-In Permanent Service | 1/4/2006 | 1/5/2006 | 1/5/2006 | A | PASS |
Jack Frank
|
|
|
emmett; Phone #: ###-#### Internet Inspection Request from: Barbara Moore r/i ok p/s u/g new ok
|
Rough-In Permanent Service | 1/3/2006 | 1/4/2006 | 1/4/2006 | A | FAIL |
Jack Frank
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. met contractor 210.52(A&B) needs outlet kit wall by pantry door, and upstairs along rail, 300.4(A)(1)&(D) high and low voltages, 314.16 box fill every where, 250.148 grd all metal boxes, 250.122 needs #12 equip grd for #12 circuits
|
Electrical Rough-In | 12/28/2005 | 12/29/2005 | 12/29/2005 | P | NR |
Jack Frank
|
|
|
###-#### - EMMETT contractor called
|