Final | 3/14/2006 | 3/15/2006 | 3/15/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook ok to final, signed occ card
|
Final | 3/1/2006 | 3/2/2006 | 3/2/2006 | A | PART |
Bob Reichert
|
|
|
Jeremy; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong talked to elect, ok to cover ceiling, need to see insta-hot and front areas when done, also check to see how projectors and misc equipment gets installed. rest ok
|
Final | 2/28/2006 | 3/1/2006 | 3/1/2006 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/28/2006 at 12:25:26 PM. Contact: ###-####. do not cover ceiling, met elect, left correction notice to owner 725.8 cables shall be installed such that the building will not damage cable. Such cables shall be supported by straps or hangers or similar fittings designed and installed so as to not damage the cable. 800.24 communications cable shall be installed per 300.11 and not be supported by ceiling grid
|
Electrical Rough-In | 1/12/2006 | 1/13/2006 | 1/13/2006 | A | PASS |
Bob Reichert
|
|
|
jeremy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa walls ok to cover, hard lid ceiling ok to cover
|
Permanent Service | 12/29/2005 | 12/30/2005 | 12/30/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook p/s, exst meter pak, n, ok
|