Final | 1/24/2006 | 1/25/2006 | 1/25/2006 | A | PASS |
Jack Frank
|
|
|
added arch fault for bedroom; Phone #: ###-#### Internet Inspection Request from: Dana Moyer
|
Final | 1/20/2006 | 1/23/2006 | 1/23/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr, left corr notice, 210.11(C)(3) bathroom shall be on 20A ckt,210.12(A) bedroom shall be protected by AFCI, 110.3(B) equipment shall be installed and used in accordance with instructions
|
Electrical Rough-In | 1/3/2006 | 1/3/2006 | 1/3/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr to add back gec clamp, ric ok for walls, clg
|