Final | 6/21/2006 | 6/21/2006 | 6/21/2006 | P | PASS |
Jack Frank
|
|
|
neil; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
|
Permanent Service | 5/11/2006 | 5/11/2006 | 5/11/2006 | P | PASS |
Pat Lass
|
|
|
Neil ###-#### P/S U/G N Ok
|
Conference | 5/3/2006 | 5/3/2006 | 5/3/2006 | P | DONE |
Jack Frank
|
|
|
nel; Phone #: ###-#### Please call 1/2 hr prior Internet Inspection Request from: Cathy Chiles called discussed corections posted
|
Electrical Rough-In | 5/1/2006 | 5/2/2006 | 5/2/2006 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/1/2006 at 11:37:41 AM. Contact: ###-####. corr. called 110.3(A&B) shall install floor heat per manufactures instructions leads and sensing probe, BCC south side covered before inspection
|
Electrical Rough-In | 1/18/2006 | 1/18/2006 | 1/18/2006 | P | PASS |
Jack Frank
|
|
|
neil ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i both units ok corrections made
|
Conference | 1/18/2006 | 1/18/2006 | 1/18/2006 | P | DONE |
Jack Frank
|
|
|
neil ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
|
Electrical Rough-In | 1/17/2006 | 1/17/2006 | 1/17/2006 | P | FAIL |
Jack Frank
|
|
|
neal; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not made nail plates and 11/4" cor. posted called
|
Electrical Rough-In | 1/12/2006 | 1/13/2006 | 1/13/2006 | A | FAIL |
Jack Frank
|
|
|
neil; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections not made called reinspection fee due
|
Rough-In Permanent Service | 1/9/2006 | 1/10/2006 | 1/10/2006 | A | FAIL |
Jack Frank
|
|
|
neal; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor. do not cover both units called, 300.4 nail plates and 11/4", 314.16 box fill , 334.23 protect romex attic accesses, 210.52 outlets for wall space liv rm by pantry pomona unit kit wall by pantry reawy init, 110.12 replace plastic boxes with extra KOs broken out, only one p/s this is a duplex both p/s inspected, protect panels
|