Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE06-00094
StatusFinaled
Name GOODMAN ELECTRIC
Site Address 3704 N NORTH ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/11/20061/12/20061/12/2006APASS
DetailsPat Lass
roger ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Final1/10/20061/10/20061/10/2006PFAIL
DetailsPat Lass
roger goodman ###-####
210.12 Arc-Fault Circuit-Interrupter Protection.
(B) Dwelling Unit Bedrooms. All branch circuits that supply 125-volt, single-phase, 15- and 20-ampere outlets installed in dwelling unit bedrooms shall be protected by an arc-fault circuit interrupter

Boise city code 4-05-54
Code violations not to be retained.

300.11 Securing and Supporting.
(A) Secured in Place. Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place.
300.10 Electrical Continuity of Metal Raceways and Enclosures.
Metal raceways, cable armor, and other metal enclosures for conductors shall be metallically joined together into a continuous electric conductor and shall be connected to all boxes,
300.15 Boxes, Conduit Bodies, or Fittings - Where Required.
Fittings and connectors shall be used only with the specific wiring methods for which they are designed and listed.