Final | 1/19/2007 | 1/22/2007 | 1/22/2007 | A | PASS |
Bob Reichert
|
|
|
william; Phone #: ###-#### Internet Inspection Request from: Darla Downs called, left message, told owner to id 2 breakers, ok to final
|
Electrical Rough-In | 1/17/2007 | 1/18/2007 | 1/18/2007 | A | PASS |
Bob Reichert
|
|
|
WILLIAM; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
|
Electrical Rough-In | 1/9/2007 | 1/10/2007 | 1/10/2007 | A | FAIL |
Bob Reichert
|
|
|
william ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called gave corr notice, nec 312.5 all conductors entering enclosure shall have abrasion protection,200.6(B) grounded conductor shall be identified, nm cable shall not be stapled on edge, BCC all make-up shall be done, shall see u/g before cover, all boxes shall be installed
|
Electrical Rough-In | 1/8/2007 | 1/8/2007 | 1/8/2007 | P | NH |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/8/2007 at 11:00:58 AM. Contact: ###-####. callrd, left message to reschedule, left card
|
ELE-Request for Extension | 7/11/2006 | 10/23/2006 | | A | |
Jim Schmer
|
|
|
wiiliam jennings not finished with the work yet//7/11/06//blb
|