Temporary Service | 1/18/2006 | 1/19/2006 | 1/19/2006 | P | PASS |
Bob Reichert
|
|
|
re-inspection on temp power for temp trailers. Please call if any further problems; Phone #: ###-#### Internet Inspection Request from: todd hall corrections made, t/s o/h n ok
|
Temporary Service | 1/18/2006 | 1/18/2006 | 1/18/2006 | P | FAIL |
Bob Reichert
|
|
|
inspection for temp power for temp trailer. I (Todd Hall) spoke with Jim Schmer about placing the temp power for the trailer, on the Firestation building. Please call me if any questions; Phone #: ###-#### Internet Inspection Request from: todd hall called contr, left corr notice,312.5 conductors entering enclosures shall have abrasion protection,250.92(B)(4) bonding jumpers shall be used around concentrics, 230.2(E) service disconnects shall be identified, 408.4 circuit directory shall be supplied at tlr #1, 352.30 rnc shall be supported at tlr #1, 408.7 unused openings shall be closed at tlr #2, 110.12(A) conduit openings shall be closed at tlr #2
|