Final | 3/27/2006 | 3/27/2006 | 3/27/2006 | P | PASS |
Bob Reichert
|
|
|
Alan -- call 1st for garage access code; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corr made, ok to final
|
Final | 3/21/2006 | 3/22/2006 | 3/22/2006 | A | FAIL |
Bob Reichert
|
|
|
allen -call 1st for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, 408.4 every circuit shall be legibly identified as to its clear, evident, and specific purpose, 314.23 enclosures in finished surfaces shall be rigidly secured (floor and backsplash in kitchen),314.25 each box shall have a cover (closet), BCC walls shall have 3' access for receptacle testing in garage,and closet shelves shall be installed for final inspection to verify light clearance
|
Rough-In Permanent Service | 1/20/2006 | 1/20/2006 | 1/20/2006 | A | PASS |
Bob Reichert
|
|
|
forgot to add in 1-13-06 the following: ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 1/12/2006 | 1/13/2006 | 1/13/2006 | A | PASS |
Bob Reichert
|
|
|
###-#### allen called contr, left survey, 312.5 conductors entering enclosures shall have abrasion protection, 430.107 pump motor disconnect in tub shall be readily accessible
|