Permit Information
Permit NumberELE06-00134
StatusFinaled
Name LEE BRAITHWAIT
Site Address 1702 W FAIRVIEW AVE
Project NameKING BLDG
Customer Number 
ePlanReview 
Description
Full remodel 2-story new 400 amp service w/2 sub panes per initial cert of value $14,000///1/12/06 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/16/20065/16/20065/16/2006APASS
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Kevin Braithwait
Final5/15/20065/15/20065/15/2006PFAIL
DetailsPat Lass
kevin ###-#### re-insp
not all boxes changed out yet
Final5/14/20065/15/20065/15/2006APART
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Kevin Braithwait
downstairs ok
upstairs light boxes not open.
Final5/12/20065/12/20065/12/2006AFAIL
DetailsPat Lass
Dave Hanna approved energy code for lighting changes. new certificate on-site. ; Phone #: ###-#### Internet Inspection Request from: Kevin Braithwait
406.4 Receptacle Mounting.
(C) Receptacles Mounted on Covers. Front reception area.

110.3 Examination, Identification, Installation, and Use of Equipment.
400.8 Uses Not Permitted.
410.14 Connection of Electric-Discharge Luminaires (Lighting Fixtures).
Down stairs fixtures
314.27 Outlet Boxes.
Upstairs hallway fixtures
The lighting outlet boxes upstairs will be exposed on final because the cut-in boxes are being changed in the area where the ceiling was dropped.
Final5/1/20065/1/20065/1/2006PNR
DetailsWilliam E Thomas
re-inspect for everything except the lighting change - trying to get temp occp. Kevin ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
Final4/27/20064/28/20064/28/2006PFAIL
DetailsJack Frank
Will be on-site or in the area. please call before arrival. Kevin; Phone #: ###-#### Internet Inspection Request from: Kevin Braithwait corr. met contractor 314.20 box not flush with combustible finish, 314.27(C) needs listed floor boxes and covers, 408.4 circuit directory shall be specificfor purpose, shall complete all wiring, shall provide approved plans for lighting and swithing changed from approved set of plans at site or ok from structural for change
Electrical Rough-In3/19/20063/20/20063/20/2006APART
DetailsJack Frank
Will be on-site by 7:00am. rough-in for first floor.; Phone #: ###-#### Internet Inspection Request from: Kevin Braithwait
walls and hard ceilings 1st floor ok needs show window outlets in front entry area
Electrical Rough-In3/3/20063/3/20063/3/2006PPART
DetailsPat Lass
for 2nd floor only//kevin ###-####
2nd floor only
Permanent Service1/17/20061/17/20061/17/2006 PASS
DetailsWilliam E Thomas
Phone #: ###-#### Internet Inspection Request from: Kevin Braithwait
p/s u/g n ok
Permanent Service1/16/20061/16/20061/17/2006ACANC
DetailsWilliam E Thomas
Phone #: ###-#### Internet Inspection Request from: Kevin Braithwait
Permanent Service1/12/20061/13/20061/13/2006AFAIL
DetailsPat Lass
kevin; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
bond water and connect to building steel.