Final | 5/25/2006 | 5/26/2006 | 5/26/2006 | A | PASS |
Jack Frank
|
|
|
jamie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Final | 5/15/2006 | 5/16/2006 | 5/16/2006 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/15/2006 at 6:35:28 PM. Contact: ###-####. corr. called shall provide manufactures access for j tub motor and recepts, install all closet shelves and rods, outlet right of fireplace no power, outside paddle fan is it listed for outside
|
Permanent Service | 2/2/2006 | 2/3/2006 | 2/3/2006 | A | PASS |
Jack Frank
|
|
|
Jamie -- for energizing service; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong p/s u/g new ok
|
Rough-In Permanent Service | 2/1/2006 | 2/2/2006 | 2/2/2006 | A | CANC |
Mike Kinnear
|
|
|
Casey -- for ufer check; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ---- home owner called for inspection. told he was not to call for inspections the electrical contractor has to so we know the work is ready for inspection.
|
Electrical Rough-In | 1/30/2006 | 1/30/2006 | 1/30/2006 | P | PART |
Jack Frank
|
|
|
ufer ground inspection//casey ###-#### ok for dirt cover
|
Electrical Rough-In | 1/23/2006 | 1/24/2006 | 1/24/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/23/2006 at 5:00:18 PM. Contact: ###-####. r/i ok
|
Electrical Rough-In | 1/23/2006 | 1/23/2006 | 1/23/2006 | A | FAIL |
Jack Frank
|
|
|
electrode concrete cover ok only cor. posted called 300.4 nail plates,11/4, 314.16 box fill, 314.17 replace damaged cutin and 2 gang boxes with broken out clamps,210.52(A&B) needs outlet left of oven wall space, wall between kit and liv rm shall be on kit circuit, 250.52(A)(1) grd u/g water 1st 5 ft, complete all makeup
|