Final | 3/31/2006 | 3/31/2006 | 3/31/2006 | P | PASS |
William E Thomas
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
Electrical Rough-In | 3/16/2006 | 3/16/2006 | 3/16/2006 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 3/16/2006 at 7:24:49 AM. Contact: ###-####. all but two entry ways ceiling ok
|
Rough-In Permanent Service | 3/13/2006 | 3/13/2006 | 3/13/2006 | P | CANC |
William E Thomas
|
|
|
Dennis; Phone #: ###-####
|
Conference | 3/13/2006 | 3/13/2006 | 3/13/2006 | P | CANC |
William E Thomas
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa still working on correc\tions, talked about the meaning of 250.104. cancelled per inspector reschuled for permanent service instead 3:00 pm
|
Permanent Service | 3/13/2006 | 3/13/2006 | 3/13/2006 | P | PASS |
William E Thomas
|
|
|
Dennis; Phone #: ###-#### p/s u/g n ok
|
Permanent Service | 3/10/2006 | 3/10/2006 | 3/10/2006 | P | FAIL |
Pat Lass
|
|
|
Dennis; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong 250.104 Bonding of Piping Systems and Exposed Structural Steel. (A) Metal Water Piping. The metal water piping system shall be bonded as required in (1), (2), (3), or (4) of this section.
250.119 Identification of Equipment Grounding Conductors. Unless required elsewhere in this Code, equipment grounding conductors shall be permitted to be bare, covered, or insulated. Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green.
110.3 Examination, Identification, Installation, and Use of Equipment. (B) Installation and Use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.
|
Electrical Rough-In | 2/7/2006 | 2/8/2006 | 2/8/2006 | A | PART |
Pat Lass
|
|
|
This is for rough walls only, call James with any questions at 573.6373; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa walls ok
|
Electrical Rough-In | 1/20/2006 | 1/20/2006 | 1/20/2006 | P | PART |
Pat Lass
|
|
|
This is for underground conuitr inspection.call ryan with any questions.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa underground pipe ok should be checked by building inspector
|