Final | 5/18/2006 | 5/18/2006 | 5/18/2006 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 5/18/2006 at 5:57:23 AM. Contact: ###-####.
|
Electrical Rough-In | 2/2/2006 | 2/2/2006 | 2/2/2006 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 2/2/2006 at 6:54:25 AM. Contact: ###-####. corrections made ok cover ri
|
Permanent Service | 2/2/2006 | 2/2/2006 | 2/2/2006 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 2/2/2006 at 6:54:25 AM. Contact: ###-####. p/s u/g n ok
|
Rough-In Permanent Service | 1/30/2006 | 1/31/2006 | 1/31/2006 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/30/2006 at 3:59:44 PM. Contact: ###-####. called contr, asked him to call lv contr. Elect corr made, lv not done
|
Permanent Service | 1/25/2006 | 1/25/2006 | 1/25/2006 | P | FAIL |
Jack Frank
|
|
|
Internet Inspection Request from: Rowdy Monroe r/i & p/s failed cor. posted to both high and low voltage contractors called 250.148 terminate all equip grds together 2 gang box kit.,300.4 nail plates 11/4" for both high and low voltage,220.40 calc and provide p/s of required size for load, low voltage needs conn. for ent at cabinet
|