Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE06-00235
StatusFinaled
Name EXTREME ELECTRIC
Site Address 11591 W DIVIDE PASS CT
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: rough inspection
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/18/20065/18/20065/18/2006APASS
DetailsPat Lass
Scheduled by a contractor via Hello! on 5/18/2006 at 5:57:23 AM. Contact: ###-####.
Electrical Rough-In2/2/20062/2/20062/2/2006APASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 2/2/2006 at 6:54:25 AM. Contact: ###-####. corrections made ok cover ri
Permanent Service2/2/20062/2/20062/2/2006APASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 2/2/2006 at 6:54:25 AM. Contact: ###-####. p/s u/g n ok
Rough-In Permanent Service1/30/20061/31/20061/31/2006AFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 1/30/2006 at 3:59:44 PM. Contact: ###-####. called contr, asked him to call lv contr. Elect corr made, lv not done
Permanent Service1/25/20061/25/20061/25/2006PFAIL
DetailsJack Frank
Internet Inspection Request from: Rowdy Monroe r/i & p/s failed cor. posted to both high and low voltage contractors called 250.148 terminate all equip grds together 2 gang box kit.,300.4 nail plates 11/4" for both high and low voltage,220.40 calc and provide p/s of required size for load, low voltage needs conn. for ent at cabinet