Permanent Service | 1/27/2006 | 1/27/2006 | 1/27/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/27/2006 at 7:03:49 AM. Contact: ###-####. p/s o/h rec. ok
|
Final | 1/27/2006 | 1/27/2006 | 1/27/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/27/2006 at 7:03:49 AM. Contact: ###-####.
|
Permanent Service | 1/25/2006 | 1/26/2006 | 1/26/2006 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/25/2006 at 5:59:14 PM. Contact: ###-####. cor. called 312.5 conn. for GEC, 110.26(F)(1) clearence for subpane 30" wide, 110.3 use manufactures listed breakers only, 408.4 label panel, 300.3(B) all conductors shall be in same cable neutral wire run along side of cable also open splice #10, B C C no violation retained
|
Permanent Service | 1/25/2006 | 1/25/2006 | 1/25/2006 | P | NH |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/25/2006 at 6:52:33 AM. Contact: ###-####. notice posted called left message
|
Permanent Service | 1/24/2006 | 1/24/2006 | 1/24/2006 | A | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/24/2006 at 7:10:39 AM. Contact: ###-####. not ready called
|