Final | 4/7/2006 | 4/7/2006 | 4/7/2006 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/7/2006 at 10:44:27 AM. Contact: ###-####. corr made, ok to final
|
Final | 3/31/2006 | 3/31/2006 | 3/31/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/31/2006 at 7:31:49 AM. Contact: ###-####. called, left message, 314.15(A) emt connectors and couplings shall be listed for wet locations
|
Electrical Rough-In | 3/28/2006 | 3/28/2006 | 3/28/2006 | A | NH |
Bob Reichert
|
|
|
UNDERGROUND CONDUIT; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called contr, left message, couldn't get in gate, said to recall
|
Electrical Rough-In | 3/23/2006 | 3/23/2006 | 3/23/2006 | P | PASS |
Bob Reichert
|
|
|
POOL LIGHT POTTING COMPOUND; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack pool light potting ok, need to see rest of u/g before cover
|
Electrical Rough-In | 2/28/2006 | 2/28/2006 | 2/28/2006 | A | PASS |
Bob Reichert
|
|
|
EQUIPOTENTIAL GRID; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to pour for walk area
|
Electrical Rough-In | 2/14/2006 | 2/14/2006 | 2/14/2006 | A | PASS |
Bob Reichert
|
|
|
UG CONDUIT, CONDUIT IN BACK OF POOL GETS FILL AND COVERED WITH CONCRETE; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack corrections made, ok to cover u/g for pool
|
Electrical Rough-In | 2/13/2006 | 2/14/2006 | 2/14/2006 | A | CANC |
Bob Reichert
|
|
|
UG CONDUIT; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack Inspection cancelled from web by: Lee VanSchoiack
|
Electrical Rough-In | 2/12/2006 | 2/13/2006 | 2/13/2006 | A | FAIL |
Bob Reichert
|
|
|
underground conduit; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called contr, left message, left corr notice, 300.5 top of non metallic raceway shall be minimum 18" deep
|
Electrical Rough-In | 1/23/2006 | 1/23/2006 | 1/23/2006 | P | PASS |
Bob Reichert
|
|
|
POOL BONDING; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack pool bond only ok, no u/g seen
|