Final | 8/9/2009 | 8/10/2009 | 8/10/2009 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 8/9/2009 at 5:26:32 PM. Contact: ###-####. ok final note people have moved in unable to do a complete inspection
|
Electrical Rough-In | 3/30/2006 | 3/30/2006 | 3/30/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/30/2006 at 12:59:13 AM. corrections made, ok to cover
|
Electrical Rough-In | 3/28/2006 | 3/28/2006 | 3/28/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/28/2006 at 11:07:54 AM. Contact: ###-####. met owner, left corr notice,300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member 210.52(A)(1) receptacles shall be installed so that no point measured horizontally along the floor line is more than 6' from an outlet, BCC all make-up shall be done
|
Conference | 1/31/2006 | 2/1/2006 | 2/1/2006 | A | DONE |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/31/2006 at 11:09:18 PM. Contact: ###-####. looked at sub-panel location, and sump pump and agreed to afci since it will be in bedroom.
|