ELE-Aging Inspection | 2/3/2010 | 2/3/2010 | 2/8/2010 | | DONE |
Bob Reichert
|
|
|
no activity, see doc expire
|
DOC - Permit Expired | 2/8/2010 | 2/8/2010 | 2/8/2010 | A | PASS |
Bob Reichert
|
|
|
no activity, ok to doc expire
|
ELE-Aging Inspection | 12/4/2009 | 12/4/2009 | 12/4/2009 | | DONE |
Bob Reichert
|
|
|
no activity
|
Final | 12/3/2007 | 12/3/2007 | 12/3/2007 | P | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/3/2007 at 11:22:02 AM. Contact: ###-####. wrong type request, see ri, called owner
|
Electrical Rough-In | 12/3/2007 | 12/3/2007 | 12/3/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/3/2007 at 11:22:02 AM. Contact: ###-####. ok to backfill concrete encased electrode and u/g, ok to turn on power, call for final later
|
Rough-In Permanent Service | 11/27/2007 | 11/27/2007 | 11/27/2007 | P | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/27/2007 at 11:28:39 AM. Contact: ###-####. see ri, wrong type request
|
Electrical Rough-In | 11/27/2007 | 11/27/2007 | 11/27/2007 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/27/2007 at 11:27:29 AM. Contact: ###-####. corrections made, ok to pour concrete encased electrode,ric ok, no power until grounding done,
|
Electrical Rough-In | 11/26/2007 | 11/26/2007 | 11/26/2007 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/26/2007 at 7:40:09 AM. Contact: ###-####. called owner, left correction notice, nec 250.52(A)(3) concrete encased electrode shall be cleaned and anchored and formed for 2" concrete, 110.3(A) grounding electrode connector shall be approved for use (not pipe clamp), 312.5 cables entering enclosures shall have abrasion protection, not metal romex connector, but plastic acceptable, 200.6(A) shall identify grounded conductor, BCC conductors shall be secured within 12" of panel, gec, all make-up shall be done includinf tails for devices
|
Conference | 1/11/2007 | 1/16/2007 | 1/16/2007 | A | DONE |
Bob Reichert
|
|
|
Jeran ###-####//please call 30 min prior to meet you talked about gec, panel change and what to do for ri
|