Final | 12/11/2007 | 12/11/2007 | 12/11/2007 | P | PASS |
Bob Reichert
|
|
|
robert Phone #: ###-#### corrections made ok to final
|
Final | 12/10/2007 | 12/11/2007 | 12/11/2007 | A | FAIL |
Jack Frank
|
|
|
Robert Please call 30 min before going out Phone #: ###-#### corr not made
|
Final | 12/6/2007 | 12/7/2007 | 12/7/2007 | A | FAIL |
Bob Reichert
|
|
|
robert Note: please call 1/2 hr prior to be open Phone #: ###-#### met owner, left correction notice, nec 406.8(B) outdoor receptacles shall have weatherproof covers installed whether or not cord is in use, 210.12(B) dwelling unit bedrooms shall be protected by arc fault circuit interrupters, 410.8(B) closet fixtures shall have completely enclosed lamp, 410.8(D) closet fixtures shall be 12" from edge of shelves for incandescent and 6" for fluorescent
|
Electrical Rough-In | 2/14/2007 | 2/15/2007 | 2/15/2007 | A | CANC |
Bob Reichert
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Victoria Beall wrong type insp, see rip
|
Rough-In Permanent Service | 2/15/2007 | 2/15/2007 | 2/15/2007 | A | CANC |
Bob Reichert
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, told owner to get room count on permit correct-19 rooms, ric ok, p/s u/g n ok
|
Electrical Rough-In | 1/30/2007 | 1/30/2007 | 1/30/2007 | P | FAIL |
Bob Reichert
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Darla Downs met owner, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 boxes shall be flush with finished surface, 314.17(C) nm cable shall be stapled within 8" of box, NOTE: upgrade permit to 19 rooms
|