ELE-Aging Inspection | 9/1/2006 | 9/1/2006 | 9/5/2006 | | DONE |
Bob Reichert
|
|
|
see final
|
Final | 9/5/2006 | 9/5/2006 | 9/5/2006 | P | PASS |
Bob Reichert
|
|
|
corr made, ok to final
|
ELE-Aging Inspection | 6/12/2006 | 6/12/2006 | 6/16/2006 | | DONE |
Bob Reichert
|
|
|
checked with new electrician, they said they thought correction done,but need to set up inspection to see if corrections made.
|
ELE-Aging Inspection | 4/10/2006 | 4/10/2006 | 4/10/2006 | | NH |
Bob Reichert
|
|
|
went to site, no electricians there, suc
|
Temporary Service | 2/7/2006 | 2/8/2006 | 2/8/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tina Payne met elect, left corr notice, 240.81 ckt breaker handle sjall be up in on position, 250.28(A) bonding jumper shall be done with green screw supplied, 110.3(B) equipment shall be installed with instructions included
|
Temporary Service | 2/1/2006 | 2/6/2006 | 2/6/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tina Payne met contr, left corr notice, 230.24(B)(4) conductors shall have minimum 18' over public parking areas, 312.5 conductors entering enclosures shall have abrasion protection, 112.12(A) unused openings shall be closed in panel, 408.4 circuit directory shall be provided, 408.7 unused breaker openings shall be closed, 400.5(A) max current for 6/4 soow cord shall be 45 amps, note: line and load at breaker at transformer shall be line at top, load at bottom of breaker
|