Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE06-00416
StatusFinaled
Name PEAK ELECTRIC
Site Address 8485 W USTICK RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: remodel of interior, Fire Station #4 ///Final value is $50,946//10/9/06 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/28/20066/28/20066/28/2006PPASS
DetailsBob Reichert
Re-inspect for final. (strapping at panel A, GFI at kitchen). Open boxes in small office are to be finished by city (low voltage guy). Generator has UL emblem on Katolight tag. Thank you Bob.; Phone #: ###-#### Internet Inspection Request from: todd hall ok to final, signed occ card
Final6/26/20066/27/20066/27/2006APART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: todd hall called contr, left corr notice, BCC4-05-33(A)(B) equipment shall be listed and labelled by a nationally recognized testing lab,BCC no violations shall be retained,example conduit strapping, gfci outside, kitchen sinks, also need to add plates, bell, verify circuits work on north wall, ceilings ok to cover
Electrical Rough-In6/15/20066/15/20066/15/2006PNR
DetailsBob Reichert
PLEASE INSPECT FOR ABOVE CIELING ROUGH IN THIS AFTERNOON 6/15/06. CALL TODD HALL AT THE ABOVE NUMBER WITH QUESTIONS OR THE OFFICE AT ###-####; Phone #: ###-#### Internet Inspection Request from: todd hall open clg boxes, no lv pulled
Permanent Service4/26/20064/27/20064/27/2006PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: todd hall p/s u/g rec ok, told elect and contractor about nec 230.7, no feeder wire in service wireway
Permanent Service4/19/20064/20/20064/20/2006PNR
DetailsBob Reichert
Permanent service inspection for Fire Station, Please inspect later in the afternoon, We should be ready about 3:30-4pm; Phone #: ###-#### Internet Inspection Request from: todd hall looked at some of installation, the wireway was too small, the service disconnects not ready, need another ground rod, need gec bushings on metal pipe, told to call for morning inspection if ready
Electrical Rough-In3/21/20063/22/20063/22/2006PPASS
DetailsBob Reichert
Please inspect interior walls and ceilings for cover. Please see Tim on site.; Phone #: ###-#### Internet Inspection Request from: todd hall ric walls and hard lids only ok
Electrical Rough-In2/6/20062/6/20062/6/2006PPART
DetailsJack Frank
inspection for underslab conduits that stub up into the generator. underslab conduits and floor box in lounge area. Repaired underslab conduits. Firemen are living in temp trailer if building is not open, check back overhead doors.; Phone #: ###-#### Internet Inspection Request from: todd hall u/g ok