Final | 6/28/2006 | 6/28/2006 | 6/28/2006 | P | PASS |
Bob Reichert
|
|
|
Re-inspect for final. (strapping at panel A, GFI at kitchen). Open boxes in small office are to be finished by city (low voltage guy). Generator has UL emblem on Katolight tag. Thank you Bob.; Phone #: ###-#### Internet Inspection Request from: todd hall ok to final, signed occ card
|
Final | 6/26/2006 | 6/27/2006 | 6/27/2006 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: todd hall called contr, left corr notice, BCC4-05-33(A)(B) equipment shall be listed and labelled by a nationally recognized testing lab,BCC no violations shall be retained,example conduit strapping, gfci outside, kitchen sinks, also need to add plates, bell, verify circuits work on north wall, ceilings ok to cover
|
Electrical Rough-In | 6/15/2006 | 6/15/2006 | 6/15/2006 | P | NR |
Bob Reichert
|
|
|
PLEASE INSPECT FOR ABOVE CIELING ROUGH IN THIS AFTERNOON 6/15/06. CALL TODD HALL AT THE ABOVE NUMBER WITH QUESTIONS OR THE OFFICE AT ###-####; Phone #: ###-#### Internet Inspection Request from: todd hall open clg boxes, no lv pulled
|
Permanent Service | 4/26/2006 | 4/27/2006 | 4/27/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: todd hall p/s u/g rec ok, told elect and contractor about nec 230.7, no feeder wire in service wireway
|
Permanent Service | 4/19/2006 | 4/20/2006 | 4/20/2006 | P | NR |
Bob Reichert
|
|
|
Permanent service inspection for Fire Station, Please inspect later in the afternoon, We should be ready about 3:30-4pm; Phone #: ###-#### Internet Inspection Request from: todd hall looked at some of installation, the wireway was too small, the service disconnects not ready, need another ground rod, need gec bushings on metal pipe, told to call for morning inspection if ready
|
Electrical Rough-In | 3/21/2006 | 3/22/2006 | 3/22/2006 | P | PASS |
Bob Reichert
|
|
|
Please inspect interior walls and ceilings for cover. Please see Tim on site.; Phone #: ###-#### Internet Inspection Request from: todd hall ric walls and hard lids only ok
|
Electrical Rough-In | 2/6/2006 | 2/6/2006 | 2/6/2006 | P | PART |
Jack Frank
|
|
|
inspection for underslab conduits that stub up into the generator. underslab conduits and floor box in lounge area. Repaired underslab conduits. Firemen are living in temp trailer if building is not open, check back overhead doors.; Phone #: ###-#### Internet Inspection Request from: todd hall u/g ok
|