Final | 6/20/2006 | 6/20/2006 | 6/20/2006 | P | PASS |
Bob Reichert
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
Rough-In Permanent Service | 2/16/2006 | 2/16/2006 | 2/16/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 2/15/2006 | 2/15/2006 | 2/15/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl 314.16 boxes shall be of sufficient size to provide free space for all enclosed conductors, 300.4(D) nm cable shall be 1 1/4" from edge of framing member,312.5 all conductors entering enclosures shall have abrasion protection
|