Final | 12/27/2006 | 12/27/2006 | 12/27/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/27/2006 at 6:51:14 AM. Contact: ###-####. ok needs permit for hot tub contr will secure when ready
|
Final | 12/26/2006 | 12/26/2006 | 12/26/2006 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 12/26/2006 at 8:19:11 AM. Contact: ###-####. inside is ok disconnect in back for ac unit is all that is left to inspect.
|
ELE-Request for Extension | 9/27/2006 | 9/28/2006 | 9/27/2006 | A | PASS |
Jack Frank
|
|
|
###-#### - not finished to extend this permit
|
Electrical Rough-In | 8/30/2006 | 8/31/2006 | 8/31/2006 | A | PASS |
Pat Lass
|
|
|
Richard, as early as possible; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt R/I Ok Pending range approval
|
Electrical Rough-In | 8/28/2006 | 8/28/2006 | 8/28/2006 | P | FAIL |
Jack Frank
|
|
|
richard ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. met owner's son 300.4 nail plates 11/4", 210.52(B) address SABC, 250.148 splice all equip grds grd together at boxes 14 and 12, 110.2&3 cheetah boxes are not classed for fire, wall, or ceiling need info, 334.80 seperate cables through 1 hole above panel, talked to Tom A structural needs permit and work done too match they added a living rm and kit house now has 2 kitchens looks like they are making a aprtment out of attached garage told them to go back to plan check and resubmit
|
Conference | 7/21/2006 | 7/21/2006 | 7/21/2006 | P | PASS |
Mike Kinnear
|
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Darla Downs home owner needed time ext
|