Permit Information
Permit NumberELE06-00608
StatusFinaled
Name POWERBOUND ELECTRIC INC
Site Address 1395 W PARKHILL DR
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/17/20067/17/20067/17/2006PPASS
DetailsPat Lass
n/a; Phone #: ###-#### Internet Inspection Request from: TJ Sturges
Final6/29/20066/30/20066/30/2006AFAIL
DetailsBob Reichert
n/a; Phone #: ###-#### Internet Inspection Request from: TJ Sturges called, left message, left corr notice, nec 440.4 a/c shall be marked to allow max disc rating to be determined, 4314.21 drywall shall be patched at front door switch, 110.3(B) listed equip shall be installed according to mfg instructions- fan globe, mbr, jetted tub access min 15"x20", 210.52(A)(1) recpts shall be provided in wall space at desk top of stairs,BCC all equip shall be installed,disposal Note, check recpt operation in media closet
Electrical Rough-In2/24/20062/24/20062/24/2006PPASS
DetailsPat Lass
steve;cell ###-#### Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Electrical Rough-In2/22/20062/22/20062/22/2006PFAIL
DetailsPat Lass
nicole; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
box overfilled in kitchen and required receps upstairs still no print.
Rough-In Permanent Service2/21/20062/21/20062/21/2006PFAIL
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Nicole Richardson
boxes overfilled in garage and dinning room.
requires outlets upstairs and east outside wall. No plans on site.
Permanent Service2/21/20062/21/20062/21/2006PPASS
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: Nicole Richardson
P/S U/G N Ok