Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE06-00616
StatusFinaled
Name COCHRAN BROADWAY ELECTRIC
Site Address 10751 W OVERLAND RD
Project NameFRED MEYER
Customer Number 
ePlanReview 
Description
change porduce lighting over tables, change out deli cases, install olive cart & soup island, wire new Tully's coffe kiosk per initial cert of value $51,500//2/21/06 LEG ///Final value is no change//7/20/06 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/1/20066/2/20066/2/2006APASS
DetailsJack Frank
chad; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
ok card signed corr. made
Final5/31/20066/1/20066/1/2006PFAIL
DetailsWilliam E Thomas
chad; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
1. 314.28A1--- Need to properly size j-box for feeder pull.
2. 300.11A--- Raceways shall have thier own support wires and be identified.
3. 110.26--- working clearences for the sub-panel.
Electrical Rough-In4/3/20064/4/20064/4/2006PPASS
DetailsWilliam E Thomas
Todd -- underground slab cover; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
ok to cover with concrete.