Final | 11/22/2006 | 11/22/2006 | 11/22/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok to final
|
ELE-Aging Inspection | 10/5/2006 | 10/5/2006 | 10/5/2006 | | PART |
Jack Frank
|
|
|
wsuc
|
Rough-In Permanent Service | 4/24/2006 | 4/24/2006 | 4/24/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr. made r/i ok p/s u/g new ok
|
Rough-In Permanent Service | 4/21/2006 | 4/21/2006 | 4/21/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr. called 300.4 needs nail plates, 334.30,314.17 staple romex within 8" of boxes,250.70 use acorn or listed pipe grd clamp for GEC at rebar loose, 250.64(C) shall not splice GEC
|