Permanent Service | 3/2/2006 | 3/3/2006 | 3/3/2006 | A | PASS |
Bob Reichert
|
|
|
tom jones; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met owner, removed rack in front of panel, he is getting panel door, p/s o/h rec ok, ok to final
|
Final | 3/3/2006 | 3/3/2006 | 3/3/2006 | A | PASS |
Bob Reichert
|
|
|
see p/s
|
Final | 3/1/2006 | 3/2/2006 | 3/2/2006 | A | FAIL |
Jack Frank
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. not made 110.26 clearence for p/s, 250.8 no SMS zinsco subpanel, also reove white grd wire attached to panel,310.16 needs breaker for subpanel in laundry rm 408.4 label all panels, 408.38 needs cover and dead front zinsco subpanel fee due
|
Permanent Service | 3/1/2006 | 3/1/2006 | 3/1/2006 | P | FAIL |
Jack Frank
|
|
|
###-#### - tom corr. called 230.9(A&B) clearence for o/h drop from deck, 110.26(F)(1) clearence for p/s, 250.52(A)(1) terminate GEC at 1st 5 ft where u/g pipe enters house S W downstairs bedrm, 250.24(A)(5) remove bond screw from subpanel 408.4 label panels directory, remove phone and cable from mast
|