Final | 5/11/2006 | 5/11/2006 | 5/11/2006 | P | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman
|
Rough-In Permanent Service | 3/3/2006 | 3/3/2006 | 3/3/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 3/3/2006 at 6:56:51 AM. Contact: ###-####. r/i p/s u/g new ok
|
Rough-In Permanent Service | 3/1/2006 | 3/1/2006 | 3/1/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman corr. not called 300.4 nail plates , corr. posted on bld05-02234 for low voltage 300.4(A)(1) (D) nail plates and 11/4", 362.2&6 needs connectors for ent at boxes, 800.24 low voltage cables shall be secured, and needs connectors at boxes
|
Rough-In Permanent Service | 2/28/2006 | 2/28/2006 | 2/28/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman called contr, left message, left corr notice, BCC all make-up shall be done, 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing member, 334.80 where more than 2 nm cables pass thru wood framing that is to be fire-or draft stopped the ampacity of each conductor shall be adjusted
|