Final | 6/12/2006 | 6/12/2006 | 6/12/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shane Vigil ok to final
|
Final | 5/25/2006 | 5/26/2006 | 5/26/2006 | A | NR |
Bob Reichert
|
|
|
please call if you have any ?'s I don't think the house numbers are on yet?; Phone #: ###-#### Internet Inspection Request from: Shane Vigil called contr, all ok except disposal, a/c, dishwasher, and closet lite. told to call when ready
|
Rough-In Permanent Service | 3/21/2006 | 3/22/2006 | 3/22/2006 | P | PASS |
Bob Reichert
|
|
|
Bob I will add the 2 bar boxes in the afternoon. n; Phone #: ###-#### Internet Inspection Request from: Shane Vigil corr made. ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 3/20/2006 | 3/21/2006 | 3/21/2006 | A | FAIL |
Bob Reichert
|
|
|
please call if you have questions, thanks.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil called contr, left corr notice,334.30 nm cable shall be secured within 12" of panel, 314.20 in walls of combustible material, boxes shall be flush with finished surface,210.52(E) recpt shall be installed at front of dwelling, 300.11 cable shall be securely fastened in place, not more than 2 nm cables under staple unless listed as such, BCC all make-up shall be done(grounds), also called office for room count of 13 rooms, not 3
|