Temporary Service | 3/29/2006 | 3/30/2006 | 3/30/2006 | A | PASS |
Pat Lass
|
|
|
###-#### Above number is Cell number for Justin Metcalf. All corrections have been completed and are ready for inspection.; Phone #: ###-#### Internet Inspection Request from: Justin Metcalf T/S O/H N Ok
|
Electrical Rough-In | 3/24/2006 | 3/24/2006 | 3/24/2006 | P | FAIL |
Bob Reichert
|
|
|
This inspection was missed on the first request, and we are requesting a re-inspection.; Phone #: ###-#### Internet Inspection Request from: Justin Metcalf called contr, left corr notice, fee due, 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no bent parts (door hinges), 408.4 circuit directory shall be provided, 406(B)(2)(a)receptacle shall have weatherproof cover for in-use, 250.53(G) electrode shall not be driven over 45 degree angle
|