Final | 6/9/2006 | 6/12/2006 | 6/12/2006 | A | PASS |
Jack Frank
|
|
|
code=1000; Phone #: ###-#### Internet Inspection Request from: William Zerfas ok
|
Final | 6/7/2006 | 6/8/2006 | 6/8/2006 | A | FAIL |
Jack Frank
|
|
|
code= 1000; Phone #: ###-#### Internet Inspection Request from: William Zerfas corr. called left message, 210.52(A,B) (C)(1) outlet for wall spce and countertop kit
|
Rough-In Permanent Service | 3/14/2006 | 3/15/2006 | 3/15/2006 | A | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfa ri ok p/s u/g n ok
|
Rough-In Permanent Service | 3/14/2006 | 3/14/2006 | 3/14/2006 | P | FAIL |
Jack Frank
|
|
|
permit has been changed to show 400 amp service. Thank you!; Phone #: ###-#### Internet Inspection Request from: William Zerfas corr. called 110.26(F)(1) remove phone and catv cable from below p/s, 250.64(C) shall not splice GEC in neutral bus shall be continuious
|
Rough-In Permanent Service | 3/13/2006 | 3/14/2006 | 3/14/2006 | A | FAIL |
Jack Frank
|
|
|
The service at this job has been changed from a 200amp to a 325amp. If changes on permit need to be made and we owe $, please do so and let me know! Thank you!; Phone #: ###-#### Internet Inspection Request from: William Zerfas corr. do not cover, called 250.24(A)(1) terminate GEC too bus or terminal neutral is terminated to, needs to update permit for 400 amp service, shall have only one range cable remove the extra one bld permit states no duplex or ADU people are trying to build the house with a apartent in the back of the house
|
Rough-In Permanent Service | 3/9/2006 | 3/10/2006 | 3/10/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas do not cover posted called BLD permit states no duplex or ADU house has a seperate apartment on 1st floor, if allowed p/s needs calculations I think it is too small it's only 200 amp
|