Permit NumberELE06-00790
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 405 S CAPITOL BLVD
Project NameBODO BLDG #8
Customer Number 
ePlanReview 
Description
3-7-06 Fidelity Property Improv - Sparks Contracting - light fixtures, fire alarm, hook up restaurant equip, new service, misc plugs & switches; Owner Supplied Equipment; Cert of Value $50,270.00 eus
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/8/20066/8/20066/8/2006PPASS
DetailsBob Reichert
Call Mike w/ Doherty @ ###-#### for questions. Scheduled by Heather w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to final, signed occ card
Final6/8/20066/9/20066/8/2006ACANC
DetailsBob Reichert
Re-insp. Call Mike w/ Doherty @ ###-#### for questions. Scheduled by Heather w/ Doherty.; Phone #: ###-#### Internet Inspection Request from: Heather Packer Inspection cancelled from web by: Heather Packer
Final6/7/20066/7/20066/7/2006PNR
DetailsBob Reichert
For questions please call Mike w/ Doherty @ ###-####. Scheduled by Heather w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer talked to contr, needs to provide disc for hw heater, bond h&c pipes, loose recpts by cooler and bath, add gfci to cash register recpt, add covers painters took off, add cond strap, add bkr numbers
Permanent Service5/26/20065/26/20065/26/2006PPASS
DetailsBob Reichert
Questions call Mike @ ###-#### - scheduled by Heather Packer w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer p/s exst meter pak, n ok
Electrical Rough-In4/19/20064/19/20064/19/2006PPASS
DetailsBob Reichert
re-insp. for ceiling - there is access now - sorry -call Chris for questions ###-#### or Mike ###-#### scheduled by Heather w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to cover ceiling, corr made
Electrical Rough-In4/18/20064/19/20064/19/2006ANH
DetailsBob Reichert
Ceiling inspection - scheduled by Heather Packer w/ Doherty ; Phone #: ###-#### Internet Inspection Request from: Heather Packer called left card said to call when someone there
Electrical Rough-In4/17/20064/18/20064/18/2006AFAIL
DetailsBob Reichert
Ceiling insp. - as early as possible - scheduled by Heather Packer w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer called left message, left corr notice, 300.11(A) cables shall not be supported by ceiling grid unless tested as part of fire rated assembly, 725.8 class 1,2,3 cables shall be supported by straps,staples, hangars or similar fittings designed to not damage cable, 800.24 communications cables shall be installed by fittings so as to not damage cable
Electrical Rough-In3/31/20063/31/20063/31/2006PPART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Heather Packer u/g ok to use, ceiling not ready, will recall
Electrical Rough-In3/22/20063/24/20063/24/2006APART
DetailsBob Reichert
RI partial walls. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer met contr, left corr notice, 110.26(F)(1)(a) the space equal to the width and depth of the equipment and extending from the floor to the structural ceiling shall be dedicated to the electrical installation, BCC u/g shall be inspected before cover, interior walls except at panel area ok to cover anop
Electrical Rough-In3/9/20063/10/20063/10/2006APART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 3/9/2006 at 3:24:37 PM. Contact: ###-####. ok to cover walls anop, nw and column east