Temporary Service | 3/14/2006 | 3/14/2006 | 3/14/2006 | P | PASS |
Jack Frank
|
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa t/s u/g new ok
|
Temporary Service | 3/13/2006 | 3/13/2006 | 3/13/2006 | P | FAIL |
Bob Reichert
|
|
|
Dino -- reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called left message, left 1st corr notice posted, corr not all made, 312.5 not done
|
Temporary Service | 3/9/2006 | 3/10/2006 | 3/10/2006 | A | FAIL |
Bob Reichert
|
|
|
Kim; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr noice, 312.5 all conductors entering enclosure shall have abrasion protection, 250.24(A) wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected, 408.4 circuit directory shall be provided, 310.7 conductors used for direct burial shall be of a type identified for such use, BCC job id sticker shall be posted
|