Final | 6/21/2006 | 6/21/2006 | 6/21/2006 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook ok final
|
Rough-In Permanent Service | 3/14/2006 | 3/14/2006 | 3/14/2006 | P | PASS |
Mike Kinnear
|
|
|
Todd; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok cover ri p/s u/g n ok
|
Rough-In Permanent Service | 3/13/2006 | 3/13/2006 | 3/13/2006 | P | FAIL |
Mike Kinnear
|
|
|
Todd -- also ufer ground insp; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esongnec250.32(b)(2) isolated grounded conductors in sub panels nec300.4(a)(1)bored holes center of framing memeber or nail plates through out the 4 plex.nec300.4(D) supporting cable 1 1/4 inch from both sides of framing member through out the 4 plex ok cover concrete incased electrode only.
|